Responsive Image
Lutron CP-6001 Flexible Current Probe (2000A)
CP-6001-0M9AEZ_.png
LUTRON

Lutron CP-6001 Flexible Current Probe (2000A)

รหัสสินค้า

CP-6001

฿22,600.00(ไม่รวมภาษี)

ภาพรวม

ช่วงการวัด: 60 A/600 A/6000 A. Output Sensitivity: 50 mV/A, 5 mV/A, 0.5 mV/A. Output Voltage: 3 ACV Flexible probe length: 900mm โพรบวัด Current สำหรับ DW-6093SD, DW-6095SD

Index

    CP-6001 | ฟังก์ชั่นการวัด

    Flexible Current Probe (6000A)

    CP-6001 | จุดเด่น

    โพรบวัด Current สำหรับ DW-6093SD, DW-6095SD

    Flexible probe length : 900 mm ( 23.6 inch ).

    When change the new probe, the calibration procedures are not necessary to be executed.

    Signal output use the banana plugs, durable and safety.

    Power supply is from the meter (DW-6093, DW-6095 ),battery is not necessary.

    CP-6001 | ช่วงการวัด

    Measurement ranges

    60 A/600 A/6000 A, 3 ranges, switch selectable

    1st range value : 60 A

    2nd range value : 600 A

    3rd range value : 6000 A

    Accuracy

    ± 1% of range value

    * Accuracy is specified that the measured conductor's position is on the center of " Flexible current probe ".

    * 50/60 Hz..

    * 23 ± 5 ℃

    Frequency range  45 to 400 Hz.

    * Accuracy tested under 50/60 Hz.

    CP-6001 | Power Supply

    1 DC 1.5 V, AA ( UM-3 ) battery x 2 PCs

    2 AC to DC 9V power adapter ( optional ).

    3 Power supply from the meter ( DW-6093, DW-6095 ) via Power interface cable, PWCB-06 ( included ).

    * Power supply voltage from DW-6093, DW-6095 is DC 8V± 1V.

    CP-6001 | ขนาดสินค้า

    Main circuit unit : 105 x 56.5 x 33 mm. ( 4.1 x 2.2 x 1.3 inch ).

    Flexible probe : 900 mm x 14.5 mm DIA.

    35.4 inch x 0.57 inch DIA.

    Cable length : 3.3 meters ( 10.8 feet ).

    DC plug size : 5.5 mm x 2.5 mm DIA.

    523 g ( 1.2 LB ).

    CP-6001 | อุปกรณ์ที่มาในชุด

    Operating manual ...........................1 PC.

    Power interface cable, PWCB-06....... 1 PC.

    CP-6001 | อุปกรณ์เสริม

    AC to DC 9V power adapter.

    CP-6001 | ข้อมูลจำเพาะ

    Measurement ranges

    60 A/600 A/6000 A, 3 ranges, switch selectable

    1st range value : 60 A

    2nd range value : 600 A

    3rd range value : 6000 A

    Output sensitivity  100 mV/A, 10 mV/A, 1 mV/A,

    Accuracy

    ± 1% of range value

    * Accuracy is specified that the measured conductor's position is on the center of " Flexible current probe ".

    * 50/60 Hz..

    * 23 ± 5 ℃

    Frequency range  45 to 400 Hz.

    * Accuracy tested under 50/60 Hz.

    Linearity ± 0.2 % of reading value from 10 %

    to 100% of range value.

    Phase error < ± 1.5°  *50/60 Hz..

    Conductor position sensitivity  ± 2 % of range value.

    * Recommend the measured conductor position should > 25 mm ( 1" ) away from the " Probe locker ".

    External field influence  increase ± 1.5 % of range value max..

    * Recommend the distance between different " Flexibel current probe " should > 200 mm ( 8" ).

    Minimum load  100 K ohm for specified accuracy.

    Enclosure material  UL 94-V0 rated.

    Safety  IEC 1010, Categories III 600V.

    Power Supply 

    1 DC 1.5 V, AA ( UM-3 ) battery x 2 PCs

    2 AC to DC 9V power adapter ( optional ).

    3 Power supply from the meter ( DW-6093, DW-6095 ) via Power interface cable, PWCB-06 ( included ).

    * Power supply voltage from DW-6093, DW-6095 is DC 8V± 1V.

    Operating Temperature  0℃ to 50℃ ( 32℉ to 122℉ ).

    Operating Humidity  Less than 80% RH.

    FRONT PANEL DESCRIPTIONS

    Lutron CP-6001 Flexible Current Probe (2000A)

    3-1 Flexible current probe

    3-2 Probe locker

    3-3 Main circuit unit

    3-4 6000A/600A/60A range switch

    3-5 Cable

    3-6 Battery cover/Compartment

    3-7 Signal output plug ( +, red )

    3-8 Signal output plug ( -, black )

    3-9 Power LED lamp/ LoBAT indicator

    3-10 DC 9V power adapter input socket Fig. 1

    3-11 Power interface cable,PWCB-06

    ;